What to Know About Cathodic Protection in Washington
Cathodic protection, the anodes or impressed current that keep buried steel from rusting, answers to state law, not federal law, on regulated Washington tanks. Ecology's underground storage tank program enforces chapter 173-360A WAC, and only a certified service provider, or someone it directly supervises, may test. Under WAC 173-360A-0930, the Department of Ecology accepts tester certification from the International Code Council's U4 exam, NACE, the Steel Tank Institute, or another body it approves. A tester who installs a system, or makes a repair a corrosion expert specified, needs the ICC credential in particular under the WAC 173-360A-0920 table. When a Phase I review on a Washington property finds a steel tank with no CP, ask for the corrosion expert report that rule 0310 requires to excuse it.
Every regulated Washington site carries a facility compliance tag, and RCW 70A.355.020 ties that tag to corrosion protection compliance. Ecology also inspects tank systems at least every three years, so a lapsed CP test in Tacoma or Spokane tends to surface at the next visit. Homeowners sit outside all of this, because Ecology does not regulate home heating oil tanks and refers those owners to the Pollution Liability Insurance Agency. Commercial owners can compare cathodic protection companies in Washington through the Washington UST contractor listings and then confirm each tester's ICC, NACE or STI number.
Washington's annual state UST fee rose to $258.80 per tank on July 1, 2026, according to Ecology's 2026 tank fee notice. PLIA's UST loan and grant program can fund up to $2 million per UST facility under RCW 70A.345.030, with applications open through March 1, 2027. The statute lists upgrading or replacing a petroleum UST system among its uses, so ask PLIA whether corrosion work qualifies before budgeting. A rectifier adjustment counts as a repair here, which adds a corrosion expert's specification and two retests to the bill. Each Ecology checklist counts tanks and piping runs, so send the job out for Washington CP quotes with those counts and the last CP survey checklist attached.
Cathodic protection testing in Washington follows WAC 173-360A-0430: a test at installation or repair, another one to six months later, then one every three years. Impressed current sites add corrosion monitoring between tests: the rectifier is checked at least every 60 days against the last test's ranges and logged on checklist ECY 070-340. A zero or out-of-range reading gives the owner 24 hours to notify a corrosion expert or CP tester. Installing or repairing those rectifier systems also falls under chapter 19.28 RCW, the state electrical law, on top of the UST certification. Crews digging toward a suspected leak in Everett or Olympia should say which of the OSHA 40-hour HAZWOPER course options they completed.